142-148 Queen Street South

Centre Plaza Condominium Development · Redevelopment · 2024-03-13

Consultant: C.F. Crozier & Associates Inc. Model: UNKNOWN Revision: Rev.1
Credit scorecard — Mississauga bylaw

Each category awards a maximum percentage of the annual stormwater charge as credit. Evidence is extracted directly from the source PDF — no manual review.

Peak Flow
pre-vs-post controlled across multiple storms; avg reduction 8%
40%
Water Quality
TSS removal 80% (enhanced)
30%
Runoff Volume
water balance retains 6 mm on site (2% per mm, max 30% at 15 mm)
30%
Operations
combinable O&A sub-credits — not documented
0%
Net credit
Capped at 50% of annual stormwater charge
50%
Pre vs post peak discharge
Storm eventPre-dev (L/s)Post-dev (L/s)Δ
2-yr881.1845.5−4%
5-yr1,184.41,117.6−6%
10-yr1,458.81,376.5−6%
25-yr1,675.51,522.3−9%
50-yr1,872.21,654.6−12%
100-yr2,076.21,791.6−14%
Stormwater controls (11)
Underground storageSWM Detention Tank - Building 1A
Storage volume219.4 m³
Outletorifice

Allowable release rate 8.5 L/s (stormwater) + 1.4 L/s foundation drainage = 9.9 L/s total; located in basement of Building 1A

Underground storageSWM Detention Tank - Building 1B
Storage volume161.5 m³
Outletorifice

Allowable release rate 4.0 L/s (stormwater) + 1.0 L/s foundation drainage = 5.0 L/s total; located in basement of Building 1B

Underground storageSWM Detention Tank - Building 2A
Storage volume54.2 m³
Outletorifice

Allowable release rate 46.1 L/s (stormwater) + 0.9 L/s foundation drainage = 47.1 L/s total; located in basement of Building 2A

Underground storageSWM Detention Tank - Building 2B
Storage volume50.5 m³
Outletorifice

Allowable release rate 42.9 L/s (stormwater) + 0.9 L/s foundation drainage = 43.8 L/s total; located in basement of Building 2B

Underground storageSWM Detention Tank - Building 3A
Storage volume82.2 m³
Outletorifice

Allowable release rate 70.0 L/s (stormwater) + 1.4 L/s foundation drainage = 71.4 L/s total; located in basement of Building 3A

Underground storageSWM Detention Tank - Building 3B
Storage volume76.6 m³
Outletorifice

Allowable release rate 65.2 L/s (stormwater) + 1.3 L/s foundation drainage = 66.5 L/s total; located in basement of Building 3B

Underground storageSWM Detention Tank - Building 3C/D
Storage volume121.5 m³
Outletorifice

Allowable release rate 103.4 L/s (stormwater) + 2.1 L/s foundation drainage = 105.5 L/s total; located in basement of Building 3C/D

Underground storageSWM Detention Tank - Building 4
Storage volume52.3 m³
Outletorifice

Allowable release rate 44.5 L/s (stormwater) + 0.9 L/s foundation drainage = 45.4 L/s total; located in basement of Building 4

Oil-grit separatorPublic OGS - Street A downstream connection
Outletpipe

Located at downstream end of new storm sewer network within Streets A, B and C prior to connection to existing 975mm sewer in Crumbie Street

InfiltrationPark Infiltration Basin
Surface area0.100 ha

Provided in Park catchment to meet 5mm water balance requirement for park block

Rainwater harvesting / reuseRainwater Harvesting/Re-use - Private Blocks

Capture depth of 6.08mm per private block for irrigation of landscape/green-roofs or toilet flushing; integrated with SWM detention tanks

Best management practices (10)
Underground SWM detention tank/cisternOrifice flow controlOil-grit separator (OGS)Catchbasin shields (CB Shields)Litta TrapsRainwater harvesting and re-useInfiltration basin (park block)Initial abstractionGreen roof irrigation re-useToilet flushing re-use
Site characteristics & report metadata
ProjectCentre Plaza Condominium Development
Project typeRedevelopment
DeveloperDeZen Realty Company Ltd.
Existing land usecommercial and residential
Proposed land usemixed-use condominium (residential and commercial)
Site area4.24 ha
Water balance capture6.1 mm
TSS removal target80%
Allowable release rate687.6 L/s
Quality control methodparticle settling in SWM storage tanks/cisterns in each private block, private oil-grit separator units (if required at Site Plan stage), public OGS unit within Street A at downstream connection to Crumbie Street, and at-source CB Shields or Litta Traps within ROW catchbasins
Extraction audit
Confidence: high Completeness: 83% Source: 83-page PDF Extractor: PARCELFLOW v1 Validation: passed
Starter package
Download credit application package »
10-page PDF: pre-filled Form 2703, starter P.Eng report skeleton, submission checklist. Engineer reviews, adds site inspection + O&M plan, certifies + submits.
Download PDF »

How to read this page. Every value above was extracted from the source PDF by the PARCELFLOW report parser, which combines a layout-robust template detector with a validated extraction stage tuned to Ontario Functional Servicing and Stormwater Management reports. The four-category scorecard maps the parsed evidence onto Mississauga's credit bylaw. Numbers are estimates — engineering review still required before submitting a formal credit application to the City.